|
Environment
\ The Building Control Service
\ Smoke detection in the home
Smoke detection
in the home
Building Regulations
Building Regulations
require new buildings to be fitted with suitable means of giving
alarm in the event of a fire. In dwellings, smoke detectors play
a vital part in providing people with early warning to increase
their chances of escaping from a fire in the home.
Most fire deaths
occur in dwellings - 25 people died as a result of house fires in
1997 in Northern Ireland. An analysis of the Fire Brigade's Fire
Reports indicates that 13 dwellings had no smoke alarm, in 4 dwellings
the smoke alarm had been rendered inoperable because of the removal
of batteries, and in 1 property the detector had been incorrectly
positioned.
Building Regulations
require smoke detectors in new dwellings to be mains wired (detectors
that are battery operated only do not comply with Building Regulations).
However, it is accepted practice to install battery-operated smoke
detectors in existing dwellings. Additionally, smoke detectors or
smoke detection systems for dwellings should comply with BS 5446
or BS 5839 respectively - a fuller breakdown of the technical requirements
and where to locate detectors can be found below.
Types
and choice of detector
Basically there
are two types of smoke detectors:
1.
Ionisation Chamber Smoke Detectors
These are the
most appropriate for installation in halls, landings and other areas
where a fast-burning fire in adjacent rooms such as living or dining
rooms would present a greater danger to occupants than a smouldering
fire. Fast-burning fires produce smoke containing small particles
and ionisation detectors are particularly sensitive from this type
of fire.
2.
Optical Smoke Detectors
This type of
detector is more suitable for use in halls, landings and other areas
where smoke is produced in adjacent rooms by the burning of furniture,
bedding or other smouldering fires. Slow-burning fires produce smoke
containing large particles therefore where this type of fire is
envisaged optical detectors are best. Optical detectors are particularly
sensitive to steam and therefore should not be installed directly
outside bathrooms.
NOTE:
Other specialised detector types and combination detectors are available.
If in doubt you should consult a specialist for advice.
Requirements
for self-contained smoke alarms
The following
requirements should be met when installing self-contained smoke
alarms:
- At least
one self-contained smoke alarm should be installed on each storey.
- When more
than one self-contained smoke alarm is installed, they should
be interconnected so that all will be able to give audible alarm
when any one of them detects smoke.
- The maximum
number of self-contained smoke alarms being interconnected should
not exceed that given in the manufacturer's instructions.
- Self-contained
smoke alarms should be permanently wired to a circuit, which is
separately fused at the distribution board.
- Circuits
serving self-contained smoke alarms should serve no other electrical
equipment.
- Where a residual
circuit device is used, it should be dedicated only to the smoke
detector circuit, and connected in such a way that the operation
of any other residual circuit device would not isolate the smoke
detector circuit.
- Smoke detectors
should be positioned within 3m of every bedroom door.
- Smoke detectors
should be positioned within 7m from every living room or kitchen
door.
- Smoke detectors
should be provided not more than 15m apart on circulation routes
where that route is more than 15m long.
- Smoke detectors
may be placed on a wall or ceiling where designated to do so.
However, when fitted on a ceiling, detectors should not be positioned
within 300mm of a light fitting, wall or ventilation device.
- Smoke detectors
should only be fixed to surfaces that are normally at or about
ambient temperature.
- Smoke detectors
should be positioned so that they can be accessed safely and easily;
(they should not be located over stairwells for example).
- Self-contained
smoke alarms should not be located in a kitchen, garage or other
place where fumes, steam or condensation (e.g. outside bathroom
door) could give false alarms.
Latest
developments
Although not
yet mentioned in NI Building Regulations, the British Standards
Institute has published a new Code of Practice.
BS 5839 : Pt
6 : 1995 Fire Detection and Alarm Systems for Buildings - deals
comprehensively with the recommendations for the design and installation
of fire detection and alarm systems in dwellings. This code will
permit detectors to be wired into lighting circuits if a standby
power supply is available (e.g. battery back up or capacitor).
NOTE:
The requirements of BS 5839 part 6 are considered to be outside
the scope of this Guidance Document, however, detection systems
described therein would meet the requirements of Building Regulations.
Looking
after your smoke alarm
- Once a week
- press the test button to check that the detector is working;
remember that if more than one detector is fitted then they should
all alarm.
- Once every
six months - vacuum the inside of the detector. A build-up of
dust could block the detector or cause the detector to fault and
give a false alarm.
- Once a year
- change the battery.
Remember,
if you should 'trip' the main circuit breaker (RCD) at the meter
board, the smoke detector should still work.
- All detectors
should signal simultaneously if one is tested
- The smoke
detector circuit should be clearly identified at the consumer
unit/fuse box
- If the smoke
detector circuit is fitted with an on/off switch, you should ensure
that the system is switched on at all times
- When the
battery level is low the detector bleeps. Replace the battery,
do not remove it!
What
to do if your smoke alarm goes off
(as outlined in BS 5839: Part 1: 1988)
- Alert the
household and get everyone out by the safest route. If you have
to go through a smoke filled area, crawl with your head low.
- If it is
safe to do so, shut doors and windows to help reduce draughts
that could fan the fire. Feel each door before opening it - if
it is warm or if there is smoke coming through - DON'T OPEN IT
- it could be protecting you from a dangerous smouldering fire.
- Alert the
neighbours and call the fire brigade as soon as possible (don't
leave it to someone else) giving the full address of the fire.
- Make sure
that everyone stays outside the house until the fire brigade arrives
and tells you that it is safe to go back in. Possessions are replaceable
- people are not.
What
about false alarms?
If, when the
smoke alarm goes off, there is no sign of smoke, heat or noise to
indicate that there is a fire, you should get your family into a
place where escape is easy before you start investigating. If you
feel any signs of heat at the top of a door, don't open it. If the
alarm has gone off without apparent cause it may be an indication
that the battery in the smoke alarm needs replacing. Other causes
of false alarms are fumes, steam, dust and even small insects inside
the detector chamber.
Be
prepared
If you have
followed this advice you should have a smoke alarm system, which
is capable of giving you and your family warning before smoke and
fire starts to spread. This will give you and your family a better
chance to escape unharmed. The amount of warning will obviously
depend on the fire, the equipment you have chosen and how well you
have looked after it. However, you may only have a few minutes to
escape so it pays to have an escape plan in advance. Everyone, including
the children, should know what to do in the case of a real fire.
- Practice
walking along your main escape route with your family. You may
have to do it in the dark under very unpleasant conditions.
- Plan other
safe ways of escaping from your home if your main route was blocked
by fire or smoke.

|